Home   »   Produk   »   Brand ASIA   »   Omron Product   »   Relays
 
 

General Purpose Relay For Control Panel G2R-S Type

 
 
 

Untuk memesan, silahkan tekan tombol ORDER. Anda bisa memesan barang secara Online.

 

Anda juga bisa memesan via telephone. Silakan hubungi sales consultant, Hotline kami di, (021) 8690 6777 sales Consultant kami akan menjelaskan detail produk dan harga terbaru. atau email ke alamat sales@automationindo.com

 

 

Feature :

 

Lockable test button models now available.

Built-in mechanical operation indicator.

Provided with nameplate.

AC type is equipped with a coil-disconnection self-diagnostic function (LED type).

High switching power (1-pole: 10 A).

Environment-friendly (Cd, Pb free).

Wide range of Sockets also available.

 

Specifications :

 

Coil Ratings

 

 

Rated voltage Rated current* Coil
resistance*
Coil inductance (H)
(ref. value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consumption
(approx.)
50 Hz 60 Hz Armature
OFF
Armature
ON
% of rated voltage
AC 24 V 43.5 mA 37.4 mA 253 Ω 0.81 1.55 80% max. 30% max. 110% 0.9 VA at 60 Hz
110 V 9.5 mA 8.2 mA 5,566 Ω 13.33 26.83
120 V 8.6 mA 7.5 mA 7,286 Ω 16.13 32.46
230 V 4.4 mA 3.8 mA 27,172 Ω 72.68 143.9
240 V 3.7 mA 3.2 mA 30,360 Ω 90.58 182.34

 

 

Rated voltage Rated current* Coil
resistance*
Coil inductance (H)
(ref. value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consumption
(approx.)
Armature
OFF
Armature
ON
% of rated voltage
DC 6 V 87.0 mA 69 Ω 0.25 0.48 70% max. 15% min. 110% 0.53 W
12 V 43.2 mA 278 Ω 0.98 2.35
24 V 21.6 mA 1,113 Ω 3.6 8.25
48 V 11.4 mA 4,220 Ω 15.2 29.82

 

*The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±10%.

 

Contact Ratings


Number of poles 1 pole 2 poles
Load Resistive load
(cosΦ = 1)
Inductive load
(cosΦ = 0.4; L/R = 7 ms)
Resistive load
(cosΦ = 1)
Inductive load
(cosΦ = 0.4; L/R = 7 ms)
Rated load 10 A at 250 VAC;
10 A at 30 VDC
7.5 A at 250 VAC;
5 A at 30 VDC
5 A at 250 VAC;
5 A at 30 VDC
2 A at 250 VAC;
3 A at 30 VDC
Rated carry current 10 A 5 A
Max. switching voltage 440 VAC, 125 VDC 380 VAC, 125 VDC
Max. switching current 10 A 5 A
Max. switching power 2,500 VA, 300 W 1,875 VA, 150 W 1,250 VA, 150 W 500 VA, 90 W
Failure rate (reference value) 100 mA at 5 VDC 10 mA at 5 VDC

 

Note:P level: λ60 = 0.1 x 10-6/operation

 

 

Characteristics


Item 1 pole 2 poles
Contact resistance 100 mΩ max.
Operate (set) time 15 ms max.
Release (reset) time AC: 10 ms max.; DC: 5 ms max.
(w/built-in diode: 20 ms max.)
AC: 15 ms max.; DC: 10 ms max.
(w/built-in diode: 20 ms max.)
Max. operating
frequency
Mechanical: 18,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Dielectric strength 5,000 VAC, 50/60 Hz for 1 min between coil and
contacts*;
1,000 VAC, 50/60 Hz for 1 min between contacts
of same polarity
5,000 VAC, 50/60 Hz for 1 min between coil and
contacts*;
3,000 VAC, 50/60 Hz for 1 min between contacts
of different polarity
1,000 VAC, 50/60 Hz for 1 min between contacts
of same polarity
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Shock resistance Destruction: 1,000 m/s2
Malfunction: 200 m/s2 when energized; 100 m/s2 when not energized
Endurance Mechanical:
AC coil: 10,000,000 operations min.;
DC coil: 20,000,000 operations min. (at 18,000 operations/hr)
Electrical: 100,000 operations min. (at 1,800 operations/hr under rated load) (DC coil type)
Ambient temperature Operating: -40°C to 70°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85%
Weight Approx. 21 g

 

Note:Values in the above table are the initial values.