Home   »   Produk   »   Timers   »   Omron Product   »   Motor Timer
 
 

Motor Timer H2C

 
 
 

Untuk memesan, silahkan tekan tombol ORDER. Anda bisa memesan barang secara Online.

 

Anda juga bisa memesan via telephone. Silakan hubungi sales consultant, Hotline kami di, (021) 8690 6777 sales Consultant kami akan menjelaskan detail produk dan harga terbaru. atau email ke alamat sales@automationindo.com

 

 

Motor Timer H2C

DIN-sized 48 x 48 Motor Timer with Simple Operation for Switching Time Specifications

 

 

Features :

Three Motor Timers cover the wide time range of 6 s to 30 h with easy operation from the operation panel.

Five time specifications for each model with linked time display.

DIN-standard size of 48 x 48 mm.

Easily check operation with neon lamp.

Models with sockets and models with top wiring are also available.

Certified for UL and CSA safety standards.

Conforms to EN 61812-1 (except models that end with "-F") and CE Marking.


 

 

Specifications :



Time Ranges

Five time ranges are available for each timer by turning the time range selector every 60 degrees.

Note:Rated time is displayed on the window.

 

time_range.jpg

 

Ratings

 

Item H2C
Rated supply voltage
(motor and clutch)
24, 48, 100, 110, 115, 120, 200, 220, or 240 VAC (50/60 Hz) (see note)
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 4.2 VA max. (3.96 W max.)
Reset voltage 10% max. of rated supply voltage
Reset time Minimum power-opening time: 0.5 s
Minimum pulse width: 0.5 s
Control outputs 6 A at 250 VAC, resistive load (cosΦ = 1)
Mounting method Flush mounting (except for H2C-F/-FR models), surface mounting, DIN track mounting

 

Note:The front panel of the timer is color coded to identify the following supply voltage classifications:
100 to 120 V: Blue
200 to 240 V: Red
Other classes: Black

 

Characteristics

 

Accuracy of operating time ±0.5% FS max. (±1% max. at 0.2 to 6 s for the time range code B or at 0.5 to 12 s for the time range code C)
Setting error ±2% FS max.
Reset time 0.5 s max.
Influence of voltage ±1% FS max.
Influence of temperature ±2% FS max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,500 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts)
2,000 VAC, 50/60 Hz for 1 min (between contact and control circuit and between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz with 0.375-mm single amplitude for 1 h each in three directions
Malfunction: 10 to 55 Hz with 0.25-mm single amplitude for 10 min each in three directions
Shock resistance Destruction: 1,000 m/s2
Malfunction: 150 m/s2
Ambient temperature Operating: -10°C to 50°C
Storage: -25°C to 65°C
Ambient humidity Operating: 45% to 85%
Life expectancy Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 200,000 operations min. (3 A at 250 VAC, resistive load at 1,800 operations/h)
Motor life expectancy 20,000 h
Approved standards UL917, CSA C22.2 No.14.
Conforms to EN61812-1 and IEC60664-1 4 kV/1 (except for H2C-F[] models).
Output category according to EN60947-5-1 (except for H2C-F[] models).
EMC (except for H2C-F[]
models)
(EMI): EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS): EN61812-1
Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3), 8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3), 2 kV I/O signal-line (level 4)
Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3), 2 kV line to ground (level 3)
Case color Light gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight H2C series: approx. 180 g
H2C-F series: approx. 270 g